Ordinance on Preventive Fire Protection (OPFP) (VVB)
Table of Provisions (26)
Statutory Text (26 Articles)
⁶ In the field of preventive fire protection, the Fire Protection
Regulations 1-15* and Fire Protection Guidelines 10-15 to 28-15* find application
in accordance with Art. 6 of the Intercantonal Agreement on the Removal of Technical
Barriers to Trade of October 23, 1998⁴.
⁶
1. Fire Safety Authority and Competent Authority
Unless otherwise provided in para. 2, the municipal fire police is the fire safety authority and competent authority within the meaning of Fire Safety Standard 1-15 and Fire Safety Guidelines 10-15 to 28-15.
2. The Cantonal Fire Police is responsible for
a. Buildings and installations with increased fire risk according to § 3,
b. Fire Safety Standard 11-15: Art. 11 para. 1, 12 para. 2, 14 para. 2, 16, 33, 36 para. 2, 43 para. 2, 46 and 60 para. 1 (with the exception of standard concepts according to Fire Safety Guideline 10-15 "Terms and Definitions"),
c. Fire Safety Guideline 10-15: Terms "Deviations", "VKF Recognition" and "Fire Safety Authority",
d. Fire Safety Guideline 11-15: Section 2.3 para. 4 (with the exception of the determination of quality assurance level 1), 2.3 para. 5, 3.3.1 and 3.4.1 regarding deviations, as well as 5.4.1 para. 1 and 2,
e. Fire Safety Guideline 12-15: Section 7.3 para. 1,
f. Fire Safety Guideline 13-15: Section 2.5 para. 4, 3.2.5 para. 3, 3.3 para. 3 and 4.4,
* Source: Association of Cantonal Fire Insurance Companies (VKF), Bundesgasse 20, Bern; www.praever.ch
1.1.15-8 . 1. 15 - 87
1
861.12 Ordinance on Preventive Fire Safety (VVB)
g. Fire Safety Guideline 14-15: Section 3.2.7 para. 7,
h. Fire Safety Guideline 15-15: Section 4.3,
i. Fire Safety Guideline 16-15: Section 2.1 para. 3 and 2.4.4 para. 3,
j. Fire Safety Guideline 18-15: Section 3.2 and 5.1,
k. Fire Safety Guideline 19-15: Section 2.3, 3.2.1 para. 4, 3.2.3 para. 1, 3.5 para. 5, 3.7 para. 3, 3.8 para. 2, 4.3, 4.4 para. 3 and 5, 4.5 para. 1, 5.1 and 5.4 para. 3,
l. Fire Safety Guideline 20-15: Section 2.3, 3.9. para. 2, 3.10 para. 3 and 5, 3.11 para. 1, 4.1 and 4.5 para. 3,
m. Fire Safety Guideline 21-15: Section 4.3 para. 2, 4.7 para. 2 and 6.1,
n. Fire Safety Guideline 22-15: Section 2 para. 2,
o. Fire Safety Guideline 23-15: Section 4.12.1,
p. Fire Safety Guideline 26-15: Section 8.3 para. 4 and 11.3.3 para. 5,
q. Fire Safety Guideline 27-15.
Buildings and installations with increased fire risk
6 Buildings and installations with an increased fire risk within the meaning of
Art. 7 FFG include in particular those
a. where persons and property are particularly endangered due to difficult
escape routes or difficult access for the fire brigade,
b. which, due to their use or specific fire risks according to sections
3.3.1 or 3.4.1 of Fire Protection Guideline 11-15 "Quality Assurance in Fire
Protection," are assigned to quality assurance level 2 or higher,
c. where, for reasons of proportionality or nature and heritage protection, the
protection objective cannot be achieved with prescribed standard
measures.
Building
Permit
Procedure
1. If a building permit is to be issued for a structure or installation with an elevated fire risk according to § 3, the municipal fire department reviews the building application and explains which fire police conditions and requirements it deems appropriate. It transmits the building application together with the directives it intends to impose to the Cantonal Fire Department.
2. The Cantonal Fire Department determines the conditions and requirements.
Relaxations and Intensifications
1 If a relaxation or a tightening of fire
protection regulations according to Art. 11 para. 2 of Fire Protection Standard 1-15
is indicated, the municipal fire police shall submit the proposed
orders to the Cantonal Fire Police for approval.
2
Ordinance on Preventive Fire Protection (VVB)
861.12
2 The Cantonal Fire Police may exempt a municipal fire police from
the duty to submit for all or for individual areas.
B. Structural Fire Protection
6 The use of reactive fire protection systems to achieve Reactive fire
the fire resistance of structures must be noted in the land protection systems
register and requires approval from the Cantonal Fire
Police. They regulate the details in a directive.
C. Technical Fire Protection
Acceptance and
6 Project Assessment, Acceptance, and Control of Project-
Sprinkler, Fire Alarm, and Smoke Control Pressurization Systems, Fire Brigade Assessment,
Elevators, as well as the Acceptance and Control of Lightning Protection Systems Control
are carried out by the Cantonal Fire Department. It regulates the details
in directives.
Extraordinary Inspections
The Cantonal Fire Police may carry out extraordinary inspections of technical fire protection installations.
When deficiencies are identified during the acceptance or inspection of technical fire protection installations, their rectification will be ordered in writing.
1 No fees shall be charged for
a. the acceptance of newly constructed or altered installations and the
periodic inspections of installations according to § 7,
b. extraordinary inspections of technical fire protection installations
carried out by the Cantonal Fire Police,
c. initial follow-up inspections in the cases of lit. a and b,
d. the investigation of lightning strikes.
2 Other measures shall be borne by the building owner.
Costs
1. 1. 15-87
3
861.12 Ordinance on Preventive Fire Protection (VVB)
D. Operational Fire Protection
Buildings and
Installations with
Public Traffic
1 In buildings and facilities accessible to the public,
decorations are controlled by the municipal fire police. The organizer
of the event shall report the decorations
for approval in due time.
2 Decorations with a high or very high fire load
according to Fire Protection Guideline 10-15 "Terms and Definitions"
must be submitted to the municipal fire police in good time for approval.
3 For the arrangement of seating, the written approval of the municipal
fire police must be obtained on the basis of binding plans.
Safety Officer
Fire Protection
6 The management of businesses according to Art. 56 para. 1 of Fire
Protection Standard 1-15 shall, following the instructions of the Cantonal Fire
Police, draw up a duty roster in which the tasks of the fire protection officers
are defined.
Alert and
Deployment
Concepts
5 Alarm and Deployment Concepts according to Art. 45 of
Fire Protection Standard 1-15 are necessary for buildings and facilities with an increased
fire risk according to § 3.
Permits
Cleaning
Gas Appliances
and Gas
Installations
E. Thermal Installations
6 Construction, Conversion, and Operation of Thermal Installations
require, depending on their output and fuel type, an installation certificate
or a permit from the Municipal Fire Police or the Cantonal Fire Police.
The latter will regulate the details in a directive.
1 Anyone who cleans heating systems requires a permit from the Cantonal Fire Police.** The permit will be granted if the applicant holds the master diploma of the Swiss Master Chimney Sweeps Association and has legal capacity. The permit is valid for the entire cantonal territory.
**2 The Cantonal Fire Police shall issue a directive on the cleaning of heating systems.**
1 Work on gas appliances and gas installations may
only be carried out by trained specialists. The
Cantonal Fire Police may make the execution of gas installations
subject to a permit.
4
Ordinance on Preventive Fire Protection (VVB)
861.12
2 The utilities that supply gas shall periodically inspect gas appliances and
gas installations for operational safety. They may
have the inspection carried out by qualified specialists.
These specialists shall be under the supervision of the utilities and act under their
responsibility.
3 The Cantonal Fire Police shall issue directives for the inspection.
F. Hazardous Substances and Special Dangers
Protective measures must be taken for the storage and handling of hazardous protective substances to prevent fires and explosions or limit their effects. The protective measures are determined in particular by the type and quantity of the substances present.
6 1 The following permit requirements apply to hazardous substances
a. Flammable Liquids: Anyone storing more than 450 litres of flammable liquids requires a permit from the Cantonal Fire Police.
b. Flammable Gases: Anyone storing flammable gases up to 300 kilograms requires a permit from the Municipal Fire Police. For larger quantities, a permit from the Cantonal Fire Police is required.
c. Explosives and pyrotechnic articles for commercial purposes: Anyone manufacturing or storing explosives as well as pyrotechnic articles requires a permit from the Cantonal Fire Police.
d. Pyrotechnic articles for recreational purposes
1. Storage up to 300 kilograms gross and sale: Permit from the Municipal Fire Police,
2. Storage of large quantities and manufacturing: Permit from the Cantonal Fire Police.
e. Ammunition: Anyone manufacturing hunting, sporting, or industrial ammunition or storing more than 300 kilograms gross requires a permit from the Cantonal Fire Police.
2 The storage of small quantities of hazardous substances in accordance with lit. a, b, d, and e is exempt from permit requirements.
3 The Cantonal Fire Police shall regulate the details in a directive.
1. 1. 15-87
5
861.12 Ordinance on Preventive Fire Protection (VVB)
Fire Ban
1 In situations of particular danger, especially during drought or great dryness, it may be generally prohibited to ignite fireworks or open fires.
2 The cantonal forest engineer is responsible for forests and areas near forests, and the political municipalities are responsible for the remaining area.
New and
Conversion Buildings
Existing
Buildings
Immediate
Measures
Building
Register
G. Fire Police Inspections
1 The municipal fire police monitor, during new constructions and renovations, compliance with the conditions and requirements of the building permit and fire protection regulations. They carry out controls as necessary during construction and in any case after completion of the building project. Controls according to §§ 7, 8 and 15 remain reserved.
2 The Cantonal Fire Police regulate the details in a directive.
1 The municipal fire police conducts periodic or case-by-case inspections in existing buildings. Inspections according to §§ 7, 8 and 15 remain reserved.
2 For buildings and facilities with an increased fire risk according to § 3, the Cantonal Fire Police is responsible.6
3 The Cantonal Fire Police issues the necessary directives regarding inspections, taking into account the fire risk of the various building types and uses. It may subject building categories with low fire risk to the self-inspection of the building owner.
Where the risk of fire and explosion is particularly high, the necessary immediate measures shall be ordered.
The fire protection authority maintains a register of the buildings and installations subject to its control. The register contains the information relevant for fire prevention and firefighting, particularly concerning technical fire protection facilities, special sources of danger, the inspections, and identified deficiencies.
6
Ordinance on Preventive Fire Protection (VVB)
H. Final Provisions
861.12
The Cantonal Fire Police shall arrange for the updating
of the Annex to this Ordinance if the Intercantonal Body for Technical Barriers to Trade amends the enactments mentioned therein or adopts further enactments.
a. Ordinance on General Fire Protection of 18 August 1993,
b. Ordinance on Structural Fire Protection of 18 August 1993,
c. Ordinance on Building Lightning Protection of 21 August 1974.
Repeal of
Enactments
Entry into force
Annex 7
1 OS 59, 440.
2 LS 700.1.
3 LS 861.1.
4 LS 946.
5 Inserted by decision of the Cantonal Council of 12 November 2014 (OS 69, 585; ABI 2014-11-21).
In force since 1 January 2015.
6 Version in accordance with the decision of the Cantonal Council of 12 November 2014 (OS 69, 585; ABI 2014-11-21).
In force since 1 January 2015.