Art. 35 Implementing regulation of the Act of 16 May 2006 on Energy (RLVLEne) - Ventilation Installations
Art. 35 RLVLEne - Ventilation Installations · Ventilation Installations
1. The installation, replacement, or modification of ventilation systems is subject to authorization by the authority referred to in Article 120 LATC [D] when the total exhaust air flow per building equals or exceeds 1,000 m³/h.
2. For the purposes of summer cooling, solutions utilizing natural ventilation must be prioritized.
3. Dual-flow ventilation systems must be equipped with efficient heat recovery devices in accordance with the state of the art.
4. Mechanical air extraction systems for heated premises must be equipped with a controlled fresh air supply device as well as a heat recovery unit or a device for the recovery of the heat from the extracted air, provided that the exhaust air flow, per building, exceeds 1,000 m³/h and the operating time exceeds 500 hours per year. In the case of several separate simple mechanical air extraction systems located in the same building, they must be considered as a single installation.
5. …
6. …
7. Ventilation systems serving rooms or groups of rooms with significantly different purposes or operating durations must be equipped with devices allowing for differentiated operation.
8. …