Art. 21 Regulations on Energy (REn) - Ventilation Systems (Art. 16 EnGe)
Art. 21 EnR - Ventilation Systems (Art. 16 EnGe) · Ventilation Systems (Art. 16 EnGe)
1. Ventilation systems with outside air and exhaust air must be equipped with heat recovery. The temperature change efficiency must correspond to the state of the art, provided that no requirements of the EnEV apply.
2. Simple exhaust air systems from heated rooms must either be equipped with controlled supply air and heat recovery or with the use of exhaust air heat, provided the exhaust air volume flow is more than 1000 m³/h and the operating duration exceeds 500 hours per year. Several separate simple exhaust air systems in the same building are considered as one system.
3. Air speeds in equipment, relative to the net area, must not exceed 2 m/s, and in the relevant duct section, the following values must not be exceeded
a) up to 1000 m³/h: 3 m/s;
b) up to 2000 m³/h: 4 m/s;
c) up to 4000 m³/h: 5 m/s;
d) up to 10,000 m³/h: 6 m/s;
e) over 10,000 m³/h: 7 m/s.
4. Higher air speeds are permissible if it is demonstrated through proper energy consumption calculation that no increased energy consumption occurs, if these speeds are unavoidable due to individual spatial obstacles, or if the operating duration is less than 1000 hours per year.
5. Ventilation systems for rooms or groups of rooms with significantly different uses must include facilities that enable individual operation.